Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revision Previous revision
Next revision
Previous revision
documents:de4000:de4000install [2022/01/25 13:24]
twebster [9.3 ]
documents:de4000:de4000install [2022/01/25 15:10] (current)
twebster [8.2 Default 32-bit registers]
Line 1082: Line 1082:
 |  40319  |  40320  |  T5:IN32  | |  40319  |  40320  |  T5:IN32  |
  
-^  PID1  ^^^+^  PID1  ^^^  ^  PID2  ^^^ 
 +^  Register  ^  Description  ^  Note  ^  ^  Register  ^  Description  ^  Note  ^ 
 +|  40400:\\ 40401  |  Enable  |  0=Disable\\ 1=Enable  | ::: |  40430:\\ 40431  |  Enable  |  0=Disable\\ 1=Enable 
 +|  40402:\\ 40403  |  P-Factor  |    | ::: |  40432:\\ 40433  |  P-Factor  |    | 
 +|  40404:\\ 40405  |  I-Factor  |    | ::: |  40434:\\ 40435  |  I-Factor  |    | 
 +|  40406:\\ 40407  |  D-Factor      | ::: |  40436:\\ 40437  |  D-Factor      | 
 +|  40408:\\ 40409  |  Max Limit  |    | ::: |  40438:\\ 40439  |  Max Limit  |    | 
 +|  40410:\\ 40411  |  Min Limit  |    | ::: |  40440:\\ 40441  |  Min Limit  |    | 
 +|  40412:\\ 40413  |  Input\\ Terminal  |  1-5  | ::: |  40442:\\ 40443  |  Input\\ Terminal  |  1-5  | 
 +|  40414:\\ 40415  |  Input\\ Channel  |  1-32  | ::: |  40444:\\ 40445  |  Input\\ Channel  |  1-32  | 
 +|  40416:\\ 40417  |  Output\\ Terminal  |  1-5  | ::: |  40446:\\ 40447  |  Output\\ Terminal  |  1-5  | 
 +|  40418:\\ 40419  |  Output\\ Channel  |  1-32  | ::: |  40448:\\ 40449  |  Output\\ Channel  |  1-32  |  
 +|  40420:\\ 40421  |  Deadband  |    | ::: |  40450:\\ 40451  |  Deadband  |    | 
 +|  40422:\\ 40423  |  Setpoint  |    | ::: |  40452:\\ 40453  |  Setpoint  |    | 
 + 
 +^  PID3  ^^^  ^  PID4  ^^^ 
 +^  Register  ^  Description  ^  Note  ^  ^  Register  ^  Description  ^  Note  ^ 
 +|  40460:\\ 40461  |  Enable  |  0=Disable\\ 1=Enable  | ::: |  40490:\\ 40491  |  Enable  |  0=Disable\\ 1=Enable 
 +|  40462:\\ 40463  |  P-Factor  |    | ::: |  40492:\\ 40493  |  P-Factor  |    | 
 +|  40464:\\ 40465  |  I-Factor  |    | ::: |  40494:\\ 40495  |  I-Factor  |    | 
 +|  40466:\\ 40467  |  D-Factor      | ::: |  40496:\\ 40497  |  D-Factor      | 
 +|  40468:\\ 40469  |  Max Limit  |    | ::: |  40498:\\ 40499  |  Max Limit  |    | 
 +|  40470:\\ 40471  |  Min Limit  |    | ::: |  40500:\\ 40501  |  Min Limit  |    | 
 +|  40472:\\ 40473  |  Input\\ Terminal  |  1-5  | ::: |  40502:\\ 40503  |  Input\\ Terminal  |  1-5  | 
 +|  40474:\\ 40475  |  Input\\ Channel  |  1-32  | ::: |  40504:\\ 40505  |  Input\\ Channel  |  1-32  | 
 +|  40476:\\ 40477  |  Output\\ Terminal  |  1-5  | ::: |  40506:\\ 40507  |  Output\\ Terminal  |  1-5  | 
 +|  40478:\\ 40479  |  Output\\ Channel  |  1-32  | ::: |  40508:\\ 40509  |  Output\\ Channel  |  1-32  |  
 +|  40480:\\ 40481  |  Deadband  |    | ::: |  40510:\\ 40511  |  Deadband  |    | 
 +|  40482:\\ 40483  |  Setpoint  |    | ::: |  40512:\\ 40513  |  Setpoint  |    | 
 + 
 +^  PID5  ^^^  ^  PID6  ^^^ 
 +^  Register  ^  Description  ^  Note  ^  ^  Register  ^  Description  ^  Note  ^ 
 +|  40520:\\ 40521  |  Enable  |  0=Disable\\ 1=Enable  | ::: |  40550:\\ 40551  |  Enable  |  0=Disable\\ 1=Enable 
 +|  40522:\\ 40523  |  P-Factor  |    | ::: |  40552:\\ 40553  |  P-Factor  |    | 
 +|  40524:\\ 40525  |  I-Factor  |    | ::: |  40554:\\ 40555  |  I-Factor  |    | 
 +|  40526:\\ 40527  |  D-Factor      | ::: |  40556:\\ 40557  |  D-Factor      | 
 +|  40528:\\ 40529  |  Max Limit  |    | ::: |  40558:\\ 40559  |  Max Limit  |    | 
 +|  40530:\\ 40531  |  Min Limit  |    | ::: |  40560:\\ 40561  |  Min Limit  |    | 
 +|  40532:\\ 40533  |  Input\\ Terminal  |  1-5  | ::: |  40562:\\ 40563  |  Input\\ Terminal  |  1-5  | 
 +|  40534:\\ 40535  |  Input\\ Channel  |  1-32  | ::: |  40564:\\ 40565  |  Input\\ Channel  |  1-32  | 
 +|  40536:\\ 40537  |  Output\\ Terminal  |  1-5  | ::: |  40566:\\ 40567  |  Output\\ Terminal  |  1-5  | 
 +|  40538:\\ 40539  |  Output\\ Channel  |  1-32  | ::: |  40568:\\ 40569  |  Output\\ Channel  |  1-32  |  
 +|  40540:\\ 40541  |  Deadband  |    | ::: |  40570:\\ 40571  |  Deadband  |    | 
 +|  40542:\\ 40543  |  Setpoint  |    | ::: |  40572:\\ 40573  |  Setpoint  |    | 
 + 
 +^  PID7  ^^^  ^  PID8  ^^^ 
 +^  Register  ^  Description  ^  Note  ^  ^  Register  ^  Description  ^  Note  ^ 
 +|  40580:\\ 40581  |  Enable  |  0=Disable\\ 1=Enable  | ::: |  40610:\\ 40611  |  Enable  |  0=Disable\\ 1=Enable 
 +|  40582:\\ 40583  |  P-Factor  |    | ::: |  40612:\\ 40613  |  P-Factor  |    | 
 +|  40584:\\ 40585  |  I-Factor  |    | ::: |  40614:\\ 40615  |  I-Factor  |    | 
 +|  40586:\\ 40587  |  D-Factor      | ::: |  40616:\\ 40617  |  D-Factor      | 
 +|  40588:\\ 40589  |  Max Limit  |    | ::: |  40618:\\ 40619  |  Max Limit  |    | 
 +|  40590:\\ 40591  |  Min Limit  |    | ::: |  40620:\\ 40621  |  Min Limit  |    | 
 +|  40592:\\ 40593  |  Input\\ Terminal  |  1-5  | ::: |  40622:\\ 40623  |  Input\\ Terminal  |  1-5  | 
 +|  40594:\\ 40595  |  Input\\ Channel  |  1-32  | ::: |  40624:\\ 40625  |  Input\\ Channel  |  1-32  | 
 +|  40596:\\ 40597  |  Output\\ Terminal  |  1-5  | ::: |  40626:\\ 40627  |  Output\\ Terminal  |  1-5  | 
 +|  40598:\\ 40599  |  Output\\ Channel  |  1-32  | ::: |  40628:\\ 40629  |  Output\\ Channel  |  1-32  |  
 +|  40600:\\ 40601  |  Deadband  |    | ::: |  40630:\\ 40631  |  Deadband  |    | 
 +|  40602:\\ 40603  |  Setpoint  |    | ::: |  40632:\\ 40633  |  Setpoint  |    | 
 + 
 +^  PID9  ^^^  ^  PID10  ^^^ 
 +^  Register  ^  Description  ^  Note  ^  ^  Register  ^  Description  ^  Note  ^ 
 +|  40640:\\ 40641  |  Enable  |  0=Disable\\ 1=Enable  | ::: |  40670:\\ 40671  |  Enable  |  0=Disable\\ 1=Enable 
 +|  40642:\\ 40643  |  P-Factor  |    | ::: |  40672:\\ 40673  |  P-Factor  |    | 
 +|  40644:\\ 40645  |  I-Factor  |    | ::: |  40674:\\ 40675  |  I-Factor  |    | 
 +|  40646:\\ 40647  |  D-Factor      | ::: |  40676:\\ 40677  |  D-Factor      | 
 +|  40648:\\ 40649  |  Max Limit  |    | ::: |  40678:\\ 40679  |  Max Limit  |    | 
 +|  40650:\\ 40651  |  Min Limit  |    | ::: |  40680:\\ 40681  |  Min Limit  |    | 
 +|  40652:\\ 40653  |  Input\\ Terminal  |  1-5  | ::: |  40682:\\ 40683  |  Input\\ Terminal  |  1-5  | 
 +|  40654:\\ 40655  |  Input\\ Channel  |  1-32  | ::: |  40684:\\ 40685  |  Input\\ Channel  |  1-32  | 
 +|  40656:\\ 40657  |  Output\\ Terminal  |  1-5  | ::: |  40686:\\ 40687  |  Output\\ Terminal  |  1-5  | 
 +|  40658:\\ 40659  |  Output\\ Channel  |  1-32  | ::: |  40688:\\ 40689  |  Output\\ Channel  |  1-32  |  
 +|  40660:\\ 40661  |  Deadband  |    | ::: |  40690:\\ 40691  |  Deadband  |    | 
 +|  40662:\\ 40663  |  Setpoint  |    | ::: |  40692:\\ 40693  |  Setpoint  |    | 
 + 
 +^  Key Command Registers  ^^ 
 +|  Register  |  Note  | 
 +|  40700  |  Main Key Command Register\\ Write 1 for Star\\ Write 2 for Reset\\ Write 3 for Stop\\ Write 4 for Cancel Timers 
 +|  40701  |  Start Key Command\\ (Write any value to start) 
 +|  40702  |  Reset Key Command\\ (Write any value to reset) 
 +|  40703  |  Stop Key Command\\ (Write any value to stop)  | 
 +|  40704  |  Cancel Timers Key Command\\ (Write any value to Cancel Timers) 
 +|  Key Commands are 16-Bit Registers  || 
 + 
 +^  Global/Control  ^^^
 ^  Register  ^  Description  ^  Note  ^ ^  Register  ^  Description  ^  Note  ^
-|  40400:\\ 40401   Enable  |  0=Disable\\ 1=Enable +|  40800:\\ 40801  |  Input #1\\ Enable  |  0=Disable\\ 1=Enable 
-|  40402:\\ 40403  |  P-Factor     +|  40802:\\ 40803  |  Input #2\\ Enable   0=Disable\\ 1=Enable  
-|  40404:\\ 40405  |  I-Factor     | +|  40804:\\ 40805  |  Input #1\\ 0% Output     | 
-|  40406:\\ 40407  |  D-Factor   |    | +|  40806:\\ 40807  |  Input #1\\ 100% Output  |    | 
-|  40408:\\ 40409  |  Max Limit     | +|  40808:\\ 40809  |  Input #2\\ 0% Output     | 
-|  40410:\\ 40411  |  Min Limit     | +|  40810:\\ 40811  |  Input #2\\ 100% Output     | 
-|  40412:\\ 40413   Input\\ Terminal  |  1-5  | +|  40812:\\ 40813   Input #1\\ Linear/PID  |  0=Linear\\ 1=PID  | 
-|  40414:\\ 40415   Input\\ Channel  |  1-32  | +|  40814:\\ 40815  |  Input #2\\ Linear/PID  |  0=Linear\\ 1=PID  | 
-|  40416:\\ 40417   Output\\ Terminal  |  1-5  | +|  40816:\\ 40817  |  Input #1\\ Terminal  |  1-5  | 
-|  40418:\\ 40419   Output\\ Channel  |  1-32  |  +|  40818:\\ 40819   Input #1\\ Channel  |  1-32  | 
-|  40420:\\ 40421  |  Deadband     | +|  40820:\\ 40821  |  Input #2\\ Terminal  |  1-5  | 
-|  40422:\\ 40423  |  Setpoint     |+|  40822:\\ 40823  |  Input #2\\ Channel  |  1-32  | 
 +|  40824:\\ 40825   Output #1\\ Terminal  |  1-5  | 
 +|  40826:\\ 40827   Output #1\\ Channel  |  1- | 
 +|  40828:\\ 40829  |  Output #2\\ Terminal  |  1-5  | 
 +|  40830:\\ 40831  |  Output #2\\ Channel  |  1-4  | 
 +|  40832:\\ 40833  |  Output #1\\ Low     | 
 +|  40834:\\ 40835  |  Output #1\\ High     | 
 +|  40836:\\ 40837  |  Output #2\\ Low  |    | 
 +|  40838:\\ 40839  |  Output #2\\ High  |    | 
 +|  40840:\\ 40841  |  Output #1\\ Ramp Rate  |    | 
 +|  40842:\\ 40843  |  Output #2\\ Ramp Rate  |    | 
 +|  40844:\\ 40845  |  Output #1\\ Reverse Action  |  0=Normal\\ 1=Reverse 
 +|  40846:\\ 40847  |  Output #2\\ Reverse Action  |  0=Normal\\ 1=Reverse 
 +|  40848:\\ 40849  |  Input #1\\ P-Factor  |    | 
 +|  40850:\\ 40851  |  Input #1\\ I-Factor  |    | 
 +|  40852:\\ 40853  |  Input #1\\ D-Factor  |    | 
 +|  40854:\\ 40855  |  Input #2\\ P-Factor  |    | 
 +|  40856:\\ 40857  |  Input #2\\ I-Factor  |    | 
 +|  40858:\\ 40859  |  Input #2\\ D-Factor  |    | 
 +|  40860:\\ 40861  |  Auto/Manual Toggle\\ Input Terminal  |  1-5  | 
 +|  40862:\\ 40863  |  Auto/Manual Toggle\\ Input Channel  |  1-32  | 
 +|  40864:\\ 40865  |  Speed Control\\ Mode  |  0=Manual\\ 1=Auto 
 +|  40866:\\ 40867  |  Manual\\ Speed  |  value in\\ RPM  | 
 + 
 +Registers 41001 - 41998 are the Register Mirror Test Area(Any value written to these registers will be able to be read starting at register 30001. For example you can write a 32 bit value at 41001,41002 and read it at 30001, 30002) 
 + 
 +Starting at register 42000:42001 The Safety Setpoint for each channel is store. First High then Low.\\ 
 +Example: 42000:42001 is Terminal 1 Input 1 High Safety Setpoint and 42002:42003 is Terminal 1 Input 1 Low Safety Setpoint. 
 + 
 +There is 100 register spacing between channels so Terminal 1 Input 2 High and Low Safety Setpoints are registers 42100:42101 and 42102:42103 
 + 
 +This continues for 32 channels per terminal board with 5 Terminal Boards Max
  
  
Line 1166: Line 1281:
 USB en zone dangereuse. USB en zone dangereuse.
  
-==== - ====+==== - IP54 ====
 When the DE-4000 System is installed in hazardous area, it shall be installed When the DE-4000 System is installed in hazardous area, it shall be installed
 in a suitable enclosure which provides an ingress protection minimum level of in a suitable enclosure which provides an ingress protection minimum level of
 IP54 (splash protected). IP54 (splash protected).
  
-==== - ====+==== - Inputs ====
 The inputs are rated non-incendive: The inputs are rated non-incendive:
-Terminal Module – when the inputs are configured as: + 
-• “Discrete” or “Digital” inputs must be connected to passive switches only. +● Terminal Module – when the inputs are configured as: 
-• When configured as thermocouple, inputs must be connected to thermocouples only. + 
-• When connected as an analog input, inputs must not exceed 5VDC. +• “Discrete” or “Digital” inputs must be connected to passive switches only.\\ 
-• When connected as 4-20mA, inputs must not exceed 24mA. +• When configured as thermocouple, inputs must be connected to thermocouples only.\\ 
-RPM inputs – when connected to Altronic 691118-x magnetic pickup or+• When connected as an analog input, inputs must not exceed 5VDC.\\ 
 +• When connected as 4-20mA, inputs must not exceed 24mA.\\ 
 +● RPM inputs – when connected to Altronic 691118-x magnetic pickup or
 Altronic 791050-x Hall Effect pickup. Both pickups are CSA approved as Altronic 791050-x Hall Effect pickup. Both pickups are CSA approved as
-non-incendive outputs. +non-incendive outputs.\\ 
-Controller Module Discrete Inputs – when connected to dry contacts.+● Controller Module Discrete Inputs – when connected to dry contacts.
  
-==== - ==== +==== - WiFi Antenna ==== 
-WiFi Antenna – Coaxial cable leaving the system enclosure shall be routed in+ 
 +Coaxial cable leaving the system enclosure shall be routed in
 conduit or be protected by another approved Division 2 wiring method. The antenna itself shall be located in a non-hazardous area, or shall not have exposed conduit or be protected by another approved Division 2 wiring method. The antenna itself shall be located in a non-hazardous area, or shall not have exposed
 bare metal elements. bare metal elements.
Line 1191: Line 1309:
 ===== - CONNECTING VIA ETHERNET TO CONFIGURE THE DE-4000 ===== ===== - CONNECTING VIA ETHERNET TO CONFIGURE THE DE-4000 =====
  
-==== - ====+==== - General ====
 Each DE-4000 System requires configuration prior to use. The DE-4000 is a Each DE-4000 System requires configuration prior to use. The DE-4000 is a
 web-enabled smart device. Configuration of the DE-4000 is through the web web-enabled smart device. Configuration of the DE-4000 is through the web
Line 1198: Line 1316:
 with a standard RJ45 connector on both ends, is required. Ethernet Cable, with a standard RJ45 connector on both ends, is required. Ethernet Cable,
 CAT5 1.0m (39") (693221-2) is a suitable cable available from Altronic. CAT5 1.0m (39") (693221-2) is a suitable cable available from Altronic.
 +
 A network connection is required to connect the laptop PC to the DE-4000. A network connection is required to connect the laptop PC to the DE-4000.
 This can be accomplished in one of two ways, a temporary change to the TCP/ This can be accomplished in one of two ways, a temporary change to the TCP/
Line 1206: Line 1325:
 adapter is outlined below for Microsoft® Windows-based computers. The laptop adapter is outlined below for Microsoft® Windows-based computers. The laptop
 PC must have at least one Network Interface Card (NIC) installed. PC must have at least one Network Interface Card (NIC) installed.
-IP Address 98.102.65.174 is the default IP address for the DE-4000 System. + 
-The IP address of your laptop PC network interface must be set to an address of 98.102.65.x, where x is any integer from 1 to 254, excluding the +● IP Address 98.102.65.174 is the default IP address for the DE-4000 System.\\ 
-range of 160-174. +● The IP address of your laptop PC network interface must be set to an address of 98.102.65.x, where x is any integer from 1 to 254, excluding the range of 160-174.\\ 
-The IP address on your laptop PC must be set to static. The PC is typically+● The IP address on your laptop PC must be set to static. The PC is typically
 configured to obtain an IP address dynamically; if so, you will usually have configured to obtain an IP address dynamically; if so, you will usually have
-no control over its address and will have to set it to static. +no control over its address and will have to set it to static.\\ 
-Follow the procedure below for Microsoft® Windows 7 operating system: +Follow the procedure below for Microsoft® Windows 7 operating system:\\ 
-1. From the Microsoft® Windows 7 desktop, click on the Windows Button in +1. From the Microsoft® Windows 7 desktop, click on the **Windows Button** in 
-the lower left-hand corner and then click on Control Panel. +the lower left-hand corner and then click on **Control Panel**. 
-2. Click on Network and Sharing Center. + 
-3. Click on Local Area Connection. +2. Click on **Network and Sharing Center**. 
-4. Click on the Properties button. + 
-5. Click on the Internet Protocol Version 4 (TCP/IPv4) item and click on the +3. Click on **Local Area Connection**. 
-Properties button. + 
-6. Click on the Use the following IP address: option.+4. Click on the **Properties** button. 
 + 
 +5. Click on the **Internet Protocol Version 4 (TCP/IPv4)** item and click on the 
 +**Properties** button. 
 + 
 +6. Click on the **Use the following IP address:** option. 
 7. Change the IP address to 98.102.65.xxx (for example 98.102.65.115). 7. Change the IP address to 98.102.65.xxx (for example 98.102.65.115).
 +
 8. Change the Subnet Mask to 255.255.255.0. 8. Change the Subnet Mask to 255.255.255.0.
-9. Click OK. + 
-10. Click OK on the Local Area Connection Properties screen. +9. Click **OK**. 
-11. Click Close on the Local Area Connection Status screen.+ 
 +10. Click **OK** on the Local Area Connection Properties screen. 
 + 
 +11. Click **Close** on the Local Area Connection Status screen. 
 For further information, please refer to the document How to Establish an Ethernet Connection to a PLC+ Module on the Altronic website www.altronic-llc.com. For further information, please refer to the document How to Establish an Ethernet Connection to a PLC+ Module on the Altronic website www.altronic-llc.com.
-A web browser on the laptop PC is used to communicate to the DE-4000+ 
 +● A web browser on the laptop PC is used to communicate to the DE-4000
 System. Preferred browsers are Google® Chrome and Firefox. System. Preferred browsers are Google® Chrome and Firefox.
-Open the web browser and type in the IP address (98.102.65.174). The DE4000 configuration page will be loaded.+ 
 +● Open the web browser and type in the IP address (98.102.65.174). The DE4000 configuration page will be loaded.
  
 ===== - List of Figures ===== ===== - List of Figures =====