Differences
This shows you the differences between two versions of the page.
Both sides previous revision Previous revision Next revision | Previous revision | ||
documents:de4000:de4000install [2022/01/25 13:15] twebster [7.9 CONTROLLER MODULE DISCRETE INPUTS:] |
documents:de4000:de4000install [2022/01/25 15:10] (current) twebster [8.2 Default 32-bit registers] |
||
---|---|---|---|
Line 870: | Line 870: | ||
be wired as high-side or low-side configurations. The output switches will be in | be wired as high-side or low-side configurations. The output switches will be in | ||
the open (de-energized) condition when the unit is not powered. | the open (de-energized) condition when the unit is not powered. | ||
- | DSO1 – FUEL SHUTOFF: Typical use of Output 1 on the Controller Module | + | |
+ | **DS01** | ||
is for fuel shutoff. Output 1 can be used to control a 12-24 volt fuel | is for fuel shutoff. Output 1 can be used to control a 12-24 volt fuel | ||
valve either as energized to run or pulsed to shut off. | valve either as energized to run or pulsed to shut off. | ||
- | DO NOT attempt to control a C.D.-powered fuel valve directly with any | + | |
+ | **DO NOT** attempt to control a C.D.-powered fuel valve directly with any | ||
of the DSOx output switches. The C.D. ignition system exceeds the | of the DSOx output switches. The C.D. ignition system exceeds the | ||
max operating voltage of the output switch. An interposing relay and | max operating voltage of the output switch. An interposing relay and | ||
a Murphy Panel Board Adapter must be used when the Fuel Valve is a | a Murphy Panel Board Adapter must be used when the Fuel Valve is a | ||
C.D. ignition-type Murphy Fuel Valve. | C.D. ignition-type Murphy Fuel Valve. | ||
- | DS02 – IGNITION SHUTDOWN: Typical use of Output 2 on the Controller | + | |
+ | **DS02** – IGNITION SHUTDOWN: Typical use of Output 2 on the Controller | ||
Module is for Ignition Shutdown. Output 2 can be used in conjunction | Module is for Ignition Shutdown. Output 2 can be used in conjunction | ||
with the low voltage shutdown on most Altronic ignition systems. In | with the low voltage shutdown on most Altronic ignition systems. In | ||
addition DSO2 can be used to control the source power to the ignition | addition DSO2 can be used to control the source power to the ignition | ||
system using a Power Management Module. | system using a Power Management Module. | ||
- | DO NOT attempt to directly ground-out (stop) a C.D. ignition system | + | |
+ | **DO NOT** attempt to directly ground-out (stop) a C.D. ignition system | ||
with output DSO2. The C.D. ignition system shutdown lead exceeds | with output DSO2. The C.D. ignition system shutdown lead exceeds | ||
the max operating voltage of output switch DSO2. An interposing relay | the max operating voltage of output switch DSO2. An interposing relay | ||
with high current contacts must be used when grounding the shutdown lead on a C.D. ignition system. | with high current contacts must be used when grounding the shutdown lead on a C.D. ignition system. | ||
- | DO NOT connect directly to the ignition system common coil ground. | + | |
- | DSO3 – CRANK DISCONNECT: Typical use of Output 3 on the Controller Module is for crank disconnect. When auto start is configured, | + | **DO NOT** connect directly to the ignition system common coil ground. |
+ | |||
+ | **DS03** | ||
digital output 3 is used for crank disconnect. If the voltage or current | digital output 3 is used for crank disconnect. If the voltage or current | ||
requirement of the crank disconnect solenoid is greater than 52VDC or | requirement of the crank disconnect solenoid is greater than 52VDC or | ||
1.2 amp, wire DS03 to a pilot duty relay. | 1.2 amp, wire DS03 to a pilot duty relay. | ||
- | DSO4 – PRELUBE/ | + | |
+ | **DSO4** – PRELUBE/ | ||
Module is for prelube/ | Module is for prelube/ | ||
of the prelube/ | of the prelube/ | ||
Line 899: | Line 906: | ||
==== - RS-485 COMMUNICATIONS WIRING ==== | ==== - RS-485 COMMUNICATIONS WIRING ==== | ||
There are two RS-485 communication ports available on the Controller Module: | There are two RS-485 communication ports available on the Controller Module: | ||
+ | |||
RS485 1 port is used for Modbus slave data | RS485 1 port is used for Modbus slave data | ||
+ | |||
RS485 2 is used for Modbus master data. | RS485 2 is used for Modbus master data. | ||
+ | |||
The DE-4000 System can communicate to other instruments, | The DE-4000 System can communicate to other instruments, | ||
via the two serial RS-485 communication wires. Use a two-conductor | via the two serial RS-485 communication wires. Use a two-conductor | ||
Line 1072: | Line 1082: | ||
| 40319 | 40320 | T5: | | 40319 | 40320 | T5: | ||
- | ^ PID1 ^^^ | + | ^ PID1 |
+ | ^ Register | ||
+ | | 40400:\\ 40401 | Enable | ||
+ | | 40402:\\ 40403 | P-Factor | ||
+ | | 40404:\\ 40405 | I-Factor | ||
+ | | 40406:\\ 40407 | D-Factor | ||
+ | | 40408:\\ 40409 | Max Limit | | ::: | 40438:\\ 40439 | Max Limit | | | ||
+ | | 40410:\\ 40411 | Min Limit | | ::: | 40440:\\ 40441 | Min Limit | | | ||
+ | | 40412:\\ 40413 | Input\\ Terminal | ||
+ | | 40414:\\ 40415 | Input\\ Channel | ||
+ | | 40416:\\ 40417 | Output\\ Terminal | ||
+ | | 40418:\\ 40419 | Output\\ Channel | ||
+ | | 40420:\\ 40421 | Deadband | ||
+ | | 40422:\\ 40423 | Setpoint | ||
+ | |||
+ | ^ PID3 ^^^ ^ PID4 ^^^ | ||
+ | ^ Register | ||
+ | | 40460:\\ 40461 | Enable | ||
+ | | 40462:\\ 40463 | P-Factor | ||
+ | | 40464:\\ 40465 | I-Factor | ||
+ | | 40466:\\ 40467 | D-Factor | ||
+ | | 40468:\\ 40469 | Max Limit | | ::: | 40498:\\ 40499 | Max Limit | | | ||
+ | | 40470:\\ 40471 | Min Limit | | ::: | 40500:\\ 40501 | Min Limit | | | ||
+ | | 40472:\\ 40473 | Input\\ Terminal | ||
+ | | 40474:\\ 40475 | Input\\ Channel | ||
+ | | 40476:\\ 40477 | Output\\ Terminal | ||
+ | | 40478:\\ 40479 | Output\\ Channel | ||
+ | | 40480:\\ 40481 | Deadband | ||
+ | | 40482:\\ 40483 | Setpoint | ||
+ | |||
+ | ^ PID5 ^^^ ^ PID6 ^^^ | ||
+ | ^ Register | ||
+ | | 40520:\\ 40521 | Enable | ||
+ | | 40522:\\ 40523 | P-Factor | ||
+ | | 40524:\\ 40525 | I-Factor | ||
+ | | 40526:\\ 40527 | D-Factor | ||
+ | | 40528:\\ 40529 | Max Limit | | ::: | 40558:\\ 40559 | Max Limit | | | ||
+ | | 40530:\\ 40531 | Min Limit | | ::: | 40560:\\ 40561 | Min Limit | | | ||
+ | | 40532:\\ 40533 | Input\\ Terminal | ||
+ | | 40534:\\ 40535 | Input\\ Channel | ||
+ | | 40536:\\ 40537 | Output\\ Terminal | ||
+ | | 40538:\\ 40539 | Output\\ Channel | ||
+ | | 40540:\\ 40541 | Deadband | ||
+ | | 40542:\\ 40543 | Setpoint | ||
+ | |||
+ | ^ PID7 ^^^ ^ PID8 ^^^ | ||
+ | ^ Register | ||
+ | | 40580:\\ 40581 | Enable | ||
+ | | 40582:\\ 40583 | P-Factor | ||
+ | | 40584:\\ 40585 | I-Factor | ||
+ | | 40586:\\ 40587 | D-Factor | ||
+ | | 40588:\\ 40589 | Max Limit | | ::: | 40618:\\ 40619 | Max Limit | | | ||
+ | | 40590:\\ 40591 | Min Limit | | ::: | 40620:\\ 40621 | Min Limit | | | ||
+ | | 40592:\\ 40593 | Input\\ Terminal | ||
+ | | 40594:\\ 40595 | Input\\ Channel | ||
+ | | 40596:\\ 40597 | Output\\ Terminal | ||
+ | | 40598:\\ 40599 | Output\\ Channel | ||
+ | | 40600:\\ 40601 | Deadband | ||
+ | | 40602:\\ 40603 | Setpoint | ||
+ | |||
+ | ^ PID9 ^^^ ^ PID10 ^^^ | ||
+ | ^ Register | ||
+ | | 40640:\\ 40641 | Enable | ||
+ | | 40642:\\ 40643 | P-Factor | ||
+ | | 40644:\\ 40645 | I-Factor | ||
+ | | 40646:\\ 40647 | D-Factor | ||
+ | | 40648:\\ 40649 | Max Limit | | ::: | 40678:\\ 40679 | Max Limit | | | ||
+ | | 40650:\\ 40651 | Min Limit | | ::: | 40680:\\ 40681 | Min Limit | | | ||
+ | | 40652:\\ 40653 | Input\\ Terminal | ||
+ | | 40654:\\ 40655 | Input\\ Channel | ||
+ | | 40656:\\ 40657 | Output\\ Terminal | ||
+ | | 40658:\\ 40659 | Output\\ Channel | ||
+ | | 40660:\\ 40661 | Deadband | ||
+ | | 40662:\\ 40663 | Setpoint | ||
+ | |||
+ | ^ Key Command Registers | ||
+ | | Register | ||
+ | | 40700 | Main Key Command Register\\ Write 1 for Star\\ Write 2 for Reset\\ Write 3 for Stop\\ Write 4 for Cancel Timers | ||
+ | | 40701 | Start Key Command\\ (Write any value to start) | ||
+ | | 40702 | Reset Key Command\\ (Write any value to reset) | ||
+ | | 40703 | Stop Key Command\\ (Write any value to stop) | | ||
+ | | 40704 | Cancel Timers Key Command\\ (Write any value to Cancel Timers) | ||
+ | | Key Commands are 16-Bit Registers | ||
+ | |||
+ | ^ Global/ | ||
^ Register | ^ Register | ||
- | | | + | | |
- | | | + | | |
- | | | + | | |
- | | | + | | |
- | | | + | | |
- | | | + | | |
- | | | + | | |
- | | | + | | 40814:\\ 40815 | Input #2\\ Linear/ |
- | | | + | | 40816:\\ 40817 | Input #1\\ Terminal |
- | | | + | | |
- | | | + | | |
- | | | + | | 40822:\\ 40823 | Input #2\\ Channel |
+ | | 40824:\\ 40825 | ||
+ | | | ||
+ | | | ||
+ | | 40830:\\ 40831 | Output #2\\ Channel | ||
+ | | 40832:\\ 40833 | Output #1\\ Low | ||
+ | | | ||
+ | | 40836:\\ 40837 | Output #2\\ Low | | | ||
+ | | 40838:\\ 40839 | Output #2\\ High | | | ||
+ | | 40840:\\ 40841 | Output #1\\ Ramp Rate | | | ||
+ | | 40842:\\ 40843 | Output #2\\ Ramp Rate | | | ||
+ | | 40844:\\ 40845 | Output #1\\ Reverse Action | ||
+ | | 40846:\\ 40847 | Output #2\\ Reverse Action | ||
+ | | 40848:\\ 40849 | Input #1\\ P-Factor | ||
+ | | 40850:\\ 40851 | Input #1\\ I-Factor | ||
+ | | 40852:\\ 40853 | Input #1\\ D-Factor | ||
+ | | 40854:\\ 40855 | Input #2\\ P-Factor | ||
+ | | 40856:\\ 40857 | Input #2\\ I-Factor | ||
+ | | 40858:\\ 40859 | Input #2\\ D-Factor | ||
+ | | 40860:\\ 40861 | Auto/Manual Toggle\\ Input Terminal | ||
+ | | 40862:\\ 40863 | Auto/Manual Toggle\\ Input Channel | ||
+ | | 40864:\\ 40865 | Speed Control\\ Mode | 0=Manual\\ 1=Auto | ||
+ | | 40866:\\ 40867 | Manual\\ Speed | value in\\ RPM | | ||
+ | |||
+ | Registers 41001 - 41998 are the Register Mirror Test Area(Any value written to these registers will be able to be read starting at register 30001. For example you can write a 32 bit value at 41001,41002 and read it at 30001, 30002) | ||
+ | |||
+ | Starting at register 42000:42001 The Safety Setpoint for each channel is store. First High then Low.\\ | ||
+ | Example: 42000:42001 is Terminal 1 Input 1 High Safety Setpoint and 42002:42003 is Terminal 1 Input 1 Low Safety Setpoint. | ||
+ | |||
+ | There is 100 register spacing between channels so Terminal 1 Input 2 High and Low Safety Setpoints are registers 42100:42101 and 42102: | ||
+ | |||
+ | This continues for 32 channels per terminal board with 5 Terminal Boards Max | ||
===== - HAZARDOUS AREA OPERATION ===== | ===== - HAZARDOUS AREA OPERATION ===== | ||
- | ==== - ==== | + | ==== - General |
The DE-4000 Series Configurable Safety Shutdown and Control System is CSA | The DE-4000 Series Configurable Safety Shutdown and Control System is CSA | ||
(C/US) – certified for Class I, Division 2, Groups C and D areas or non-hazardous | (C/US) – certified for Class I, Division 2, Groups C and D areas or non-hazardous | ||
locations. | locations. | ||
- | # The HMI Display Module is CSA certified (C/US) with an ambient temperature range of -30°C to 80°C (-22°F to 176°F) temperature code T4 | + | |
- | # The Controller Module is CSA certified (C/US) with an ambient temperature | + | ● The HMI Display Module is CSA certified (C/US) with an ambient temperature range of -30°C to 80°C (-22°F to 176°F) temperature code T4 |
+ | |||
+ | ● The Controller Module is CSA certified (C/US) with an ambient temperature | ||
range of -40°C to 85°C (-40°F to 185°F) temperature code T4 | range of -40°C to 85°C (-40°F to 185°F) temperature code T4 | ||
- | # The Terminal Module is CSA certified (C/US) with an ambient temperature | + | |
+ | ● The Terminal Module is CSA certified (C/US) with an ambient temperature | ||
range of -40°C to 85°C (-40°F to 185°F) temperature code T3C | range of -40°C to 85°C (-40°F to 185°F) temperature code T3C | ||
+ | |||
The DE-4000 System must be installed in a suitable enclosure. | The DE-4000 System must be installed in a suitable enclosure. | ||
+ | |||
The following requirements must also be met (refer to NFPA standard no. 493): | The following requirements must also be met (refer to NFPA standard no. 493): | ||
- | # The low voltage sensor switch wires within the panel enclosure must be kept | + | |
+ | ● The low voltage sensor switch wires within the panel enclosure must be kept | ||
at least two (2) inches away from other wiring. Run the sensor switch wires | at least two (2) inches away from other wiring. Run the sensor switch wires | ||
leaving the panel in a separate conduit from all other wiring and keep them | leaving the panel in a separate conduit from all other wiring and keep them | ||
separate throughout the installation. | separate throughout the installation. | ||
- | # Wiring to the sensors must have a grade of insulation capable of withstanding | + | |
+ | ● Wiring to the sensors must have a grade of insulation capable of withstanding | ||
an AC voltage of 500 volts RMS. | an AC voltage of 500 volts RMS. | ||
- | # Sensor wires must be run in separate conduits and junction boxes from high | + | |
+ | ● Sensor wires must be run in separate conduits and junction boxes from high | ||
voltage wires such as ignition, fuel valve, and other high voltage wiring. | voltage wires such as ignition, fuel valve, and other high voltage wiring. | ||
- | ==== - ==== | + | < |
+ | <p style=" | ||
+ | < | ||
+ | components may impair intrinsic | ||
+ | safety and/or suitability for Class | ||
+ | I, Div. 2, Groups C and D. Do | ||
+ | not disconnect equipment in Div. | ||
+ | 2 environment unless power is | ||
+ | switched off or the area is known to | ||
+ | be non-hazardous. | ||
+ | |||
+ | </ | ||
+ | </ | ||
+ | ==== - Power ==== | ||
The power for the DE-4000 System must be from a Class 2 power source with | The power for the DE-4000 System must be from a Class 2 power source with | ||
transient protection or from a 24-volt battery system. | transient protection or from a 24-volt battery system. | ||
+ | |||
The DE-4000 System must be installed in accordance with the requirements of | The DE-4000 System must be installed in accordance with the requirements of | ||
the National Electrical Code (US) and the Canadian Electrical Code (Canada) | the National Electrical Code (US) and the Canadian Electrical Code (Canada) | ||
- | ==== - ==== | + | ==== - WARNINGS |
- | WARNINGS | + | |
- | # WARNING – EXPLOSION HAZARD – Substitution of components may impair | + | ● WARNING – EXPLOSION HAZARD – Substitution of components may impair |
intrinsic safety and/or suitability for Class 1, Div. 2, Groups C and D. | intrinsic safety and/or suitability for Class 1, Div. 2, Groups C and D. | ||
- | # AVERTISSEMENT – RISQUE D’EXPLOSION – La substitution de composants eutrendre ce materiel inacceptable pour les emplacements de Classe I, Division 2. | + | |
- | # WARNING – EXPLOSION HAZARD – Do not disconnect equipment in Div. | + | ● AVERTISSEMENT – RISQUE D’EXPLOSION – La substitution de composants eutrendre ce materiel inacceptable pour les emplacements de Classe I, Division 2. |
+ | |||
+ | ● WARNING – EXPLOSION HAZARD – Do not disconnect equipment in Div. | ||
2 environment unless power is switched off or the area is known to be nonhazardous. | 2 environment unless power is switched off or the area is known to be nonhazardous. | ||
- | # AVERTISSEMENT – RISQUE D’EXPLOSION – Avant de deconnecter l’equipement, | + | |
+ | ● AVERTISSEMENT – RISQUE D’EXPLOSION – Avant de deconnecter l’equipement, | ||
couper le courant ou s’assurer que l’emplacement est designe non. | couper le courant ou s’assurer que l’emplacement est designe non. | ||
- | # Warning – EXPLOSION HAZARD - Do not use USB connectors in hazardous area. | + | |
- | # AVERTISSEMENT – RISQUE D’EXPLOSION – Ne pas utiliser les connecteurs | + | ● Warning – EXPLOSION HAZARD - Do not use USB connectors in hazardous area. |
+ | |||
+ | ● AVERTISSEMENT – RISQUE D’EXPLOSION – Ne pas utiliser les connecteurs | ||
USB en zone dangereuse. | USB en zone dangereuse. | ||
- | ==== - ==== | + | ==== - IP54 ==== |
When the DE-4000 System is installed in hazardous area, it shall be installed | When the DE-4000 System is installed in hazardous area, it shall be installed | ||
in a suitable enclosure which provides an ingress protection minimum level of | in a suitable enclosure which provides an ingress protection minimum level of | ||
IP54 (splash protected). | IP54 (splash protected). | ||
- | ==== - ==== | + | ==== - Inputs |
The inputs are rated non-incendive: | The inputs are rated non-incendive: | ||
- | # Terminal Module – when the inputs are configured as: | + | |
- | • “Discrete” or “Digital” inputs must be connected to passive switches only. | + | ● Terminal Module – when the inputs are configured as: |
- | • When configured as thermocouple, | + | |
- | • When connected as an analog input, inputs must not exceed 5VDC. | + | • “Discrete” or “Digital” inputs must be connected to passive switches only.\\ |
- | • When connected as 4-20mA, inputs must not exceed 24mA. | + | • When configured as thermocouple, |
- | # RPM inputs – when connected to Altronic 691118-x magnetic pickup or | + | • When connected as an analog input, inputs must not exceed 5VDC.\\ |
+ | • When connected as 4-20mA, inputs must not exceed 24mA.\\ | ||
+ | ● RPM inputs – when connected to Altronic 691118-x magnetic pickup or | ||
Altronic 791050-x Hall Effect pickup. Both pickups are CSA approved as | Altronic 791050-x Hall Effect pickup. Both pickups are CSA approved as | ||
- | non-incendive outputs. | + | non-incendive outputs.\\ |
- | # Controller Module Discrete Inputs – when connected to dry contacts. | + | ● Controller Module Discrete Inputs – when connected to dry contacts. |
+ | |||
+ | ==== - WiFi Antenna ==== | ||
- | ==== - ==== | + | Coaxial cable leaving the system enclosure shall be routed in |
- | WiFi Antenna – Coaxial cable leaving the system enclosure shall be routed in | + | |
conduit or be protected by another approved Division 2 wiring method. The antenna itself shall be located in a non-hazardous area, or shall not have exposed | conduit or be protected by another approved Division 2 wiring method. The antenna itself shall be located in a non-hazardous area, or shall not have exposed | ||
bare metal elements. | bare metal elements. | ||
Line 1154: | Line 1309: | ||
===== - CONNECTING VIA ETHERNET TO CONFIGURE THE DE-4000 ===== | ===== - CONNECTING VIA ETHERNET TO CONFIGURE THE DE-4000 ===== | ||
- | ==== - ==== | + | ==== - General |
Each DE-4000 System requires configuration prior to use. The DE-4000 is a | Each DE-4000 System requires configuration prior to use. The DE-4000 is a | ||
web-enabled smart device. Configuration of the DE-4000 is through the web | web-enabled smart device. Configuration of the DE-4000 is through the web | ||
Line 1161: | Line 1316: | ||
with a standard RJ45 connector on both ends, is required. Ethernet Cable, | with a standard RJ45 connector on both ends, is required. Ethernet Cable, | ||
CAT5 1.0m (39") (693221-2) is a suitable cable available from Altronic. | CAT5 1.0m (39") (693221-2) is a suitable cable available from Altronic. | ||
+ | |||
A network connection is required to connect the laptop PC to the DE-4000. | A network connection is required to connect the laptop PC to the DE-4000. | ||
This can be accomplished in one of two ways, a temporary change to the TCP/ | This can be accomplished in one of two ways, a temporary change to the TCP/ | ||
Line 1169: | Line 1325: | ||
adapter is outlined below for Microsoft® Windows-based computers. The laptop | adapter is outlined below for Microsoft® Windows-based computers. The laptop | ||
PC must have at least one Network Interface Card (NIC) installed. | PC must have at least one Network Interface Card (NIC) installed. | ||
- | # IP Address 98.102.65.174 is the default IP address for the DE-4000 System. | + | |
- | # The IP address of your laptop PC network interface must be set to an address of 98.102.65.x, | + | ● IP Address 98.102.65.174 is the default IP address for the DE-4000 System.\\ |
- | range of 160-174. | + | ● The IP address of your laptop PC network interface must be set to an address of 98.102.65.x, |
- | # The IP address on your laptop PC must be set to static. The PC is typically | + | ● The IP address on your laptop PC must be set to static. The PC is typically |
configured to obtain an IP address dynamically; | configured to obtain an IP address dynamically; | ||
- | no control over its address and will have to set it to static. | + | no control over its address and will have to set it to static.\\ |
- | Follow the procedure below for Microsoft® Windows 7 operating system: | + | Follow the procedure below for Microsoft® Windows 7 operating system:\\ |
- | 1. From the Microsoft® Windows 7 desktop, click on the Windows Button in | + | 1. From the Microsoft® Windows 7 desktop, click on the **Windows Button** in |
- | the lower left-hand corner and then click on Control Panel. | + | the lower left-hand corner and then click on **Control Panel**. |
- | 2. Click on Network and Sharing Center. | + | |
- | 3. Click on Local Area Connection. | + | 2. Click on **Network and Sharing Center**. |
- | 4. Click on the Properties button. | + | |
- | 5. Click on the Internet Protocol Version 4 (TCP/IPv4) item and click on the | + | 3. Click on **Local Area Connection**. |
- | Properties button. | + | |
- | 6. Click on the Use the following IP address: option. | + | 4. Click on the **Properties** button. |
+ | |||
+ | 5. Click on the **Internet Protocol Version 4 (TCP/IPv4)** item and click on the | ||
+ | **Properties** button. | ||
+ | |||
+ | 6. Click on the **Use the following IP address:** option. | ||
7. Change the IP address to 98.102.65.xxx (for example 98.102.65.115). | 7. Change the IP address to 98.102.65.xxx (for example 98.102.65.115). | ||
+ | |||
8. Change the Subnet Mask to 255.255.255.0. | 8. Change the Subnet Mask to 255.255.255.0. | ||
- | 9. Click OK. | + | |
- | 10. Click OK on the Local Area Connection Properties screen. | + | 9. Click **OK**. |
- | 11. Click Close on the Local Area Connection Status screen. | + | |
+ | 10. Click **OK** on the Local Area Connection Properties screen. | ||
+ | |||
+ | 11. Click **Close** on the Local Area Connection Status screen. | ||
For further information, | For further information, | ||
- | # A web browser on the laptop PC is used to communicate to the DE-4000 | + | |
+ | ● A web browser on the laptop PC is used to communicate to the DE-4000 | ||
System. Preferred browsers are Google® Chrome and Firefox. | System. Preferred browsers are Google® Chrome and Firefox. | ||
- | # Open the web browser and type in the IP address (98.102.65.174). The DE4000 configuration page will be loaded. | + | |
+ | ● Open the web browser and type in the IP address (98.102.65.174). The DE4000 configuration page will be loaded. | ||
===== - List of Figures ===== | ===== - List of Figures ===== |