Differences
This shows you the differences between two versions of the page.
| Both sides previous revision Previous revision Next revision | Previous revision | ||
|
documents:de4000:de4000install [2022/01/25 13:05] twebster [7.3 ] |
documents:de4000:de4000install [2022/01/25 15:10] (current) twebster [8.2 Default 32-bit registers] |
||
|---|---|---|---|
| Line 694: | Line 694: | ||
| </p> | </p> | ||
| </ | </ | ||
| - | ==== - ==== | + | ==== - Hardware Safety Connection (HSC) ==== |
| - | Hardware Safety Connection (HSC) | + | |
| The Hardware Safety Connection on the Terminal Module, when connected | The Hardware Safety Connection on the Terminal Module, when connected | ||
| to the Controller Module, acts as an independent shutdown signal from any | to the Controller Module, acts as an independent shutdown signal from any | ||
| Line 703: | Line 703: | ||
| a low voltage 5VDC signal. | a low voltage 5VDC signal. | ||
| - | ==== - ==== | + | ==== - INPUT SENSOR WIRING |
| - | INPUT SENSOR WIRING | + | |
| Each Terminal Module contains up to 32 sensor inputs. The sensor wire leads | Each Terminal Module contains up to 32 sensor inputs. The sensor wire leads | ||
| connect to the pluggable terminal blocks on the Terminal Module. The input | connect to the pluggable terminal blocks on the Terminal Module. The input | ||
| Line 712: | Line 712: | ||
| for multiple Terminal Modules, the board number is shown first, then the channel number separated by a colon. For example, channel 15 on terminal board | for multiple Terminal Modules, the board number is shown first, then the channel number separated by a colon. For example, channel 15 on terminal board | ||
| 1 is shown as: T1:IN15. | 1 is shown as: T1:IN15. | ||
| + | |||
| All unused inputs on the Terminal Module must have a shunt jumper in place. | All unused inputs on the Terminal Module must have a shunt jumper in place. | ||
| Each input has a 4-position mechanical switch located on the Terminal Module | Each input has a 4-position mechanical switch located on the Terminal Module | ||
| Line 717: | Line 718: | ||
| === - DISCRETE SENSOR INPUT WIRING === | === - DISCRETE SENSOR INPUT WIRING === | ||
| - | # Normally-open (N/O) sensor switches are wired with one wire to the IN+ | + | |
| + | ● Normally-open (N/O) sensor switches are wired with one wire to the IN+ | ||
| terminal of the respective sensor number and the other to engine ground | terminal of the respective sensor number and the other to engine ground | ||
| which should be the same as power minus (−). A shunt jumper must be | which should be the same as power minus (−). A shunt jumper must be | ||
| connected from the (INx+) terminal to the (INx-) terminal for normally-open | connected from the (INx+) terminal to the (INx-) terminal for normally-open | ||
| sensors. (See wiring diagrams). | sensors. (See wiring diagrams). | ||
| - | # Normally-closed (N/C) sensor switches are wired with one wire to the (INx+) | + | |
| + | ● Normally-closed (N/C) sensor switches are wired with one wire to the (INx+) | ||
| terminal and the other to the (IN-) terminal of the respective sensor number. Note that the shunt jumper must be removed. | terminal and the other to the (IN-) terminal of the respective sensor number. Note that the shunt jumper must be removed. | ||
| + | |||
| Use a wire size between 16 AWG (max.) and 24 AWG (min.) to connect | Use a wire size between 16 AWG (max.) and 24 AWG (min.) to connect | ||
| the sensor switches to the terminal strip connector. Strip the insulation | the sensor switches to the terminal strip connector. Strip the insulation | ||
| Line 734: | Line 738: | ||
| however, wires should be protected from damage by running them in a protective conduit or in sheaths where appropriate. In addition, it is essential | however, wires should be protected from damage by running them in a protective conduit or in sheaths where appropriate. In addition, it is essential | ||
| that the following practices be adhered to: | that the following practices be adhered to: | ||
| + | |||
| A. Never run sensor wires in the same conduit with ignition wiring or | A. Never run sensor wires in the same conduit with ignition wiring or | ||
| other high energy wiring such as the AC line power. | other high energy wiring such as the AC line power. | ||
| + | |||
| B. Keep secondary wires to spark plugs and other high voltage wiring at | B. Keep secondary wires to spark plugs and other high voltage wiring at | ||
| least eight inches (200mm) away from sensor and sensor wiring. | least eight inches (200mm) away from sensor and sensor wiring. | ||
| - | C. Sensor switches may be connected to any passive device using contacts such as standard switch gauges, pressure or level switches. DO | + | |
| - | NOT connect sensor leads to any voltage producing element. | + | C. Sensor switches may be connected to any passive device using contacts such as standard switch gauges, pressure or level switches. |
| D. In the case of a field conversion, where sensors have previously been | D. In the case of a field conversion, where sensors have previously been | ||
| used with Murphy tattletales, | used with Murphy tattletales, | ||
| Line 745: | Line 752: | ||
| contacts may be burned or pitted from past exposure to ignition | contacts may be burned or pitted from past exposure to ignition | ||
| system primary voltage. It is advisable to replace such sensors. | system primary voltage. It is advisable to replace such sensors. | ||
| + | |||
| E. If it becomes necessary to check sensor switch to panel wiring with | E. If it becomes necessary to check sensor switch to panel wiring with | ||
| an ohmmeter or other checker, first DISCONNECT the plug-in terminal | an ohmmeter or other checker, first DISCONNECT the plug-in terminal | ||
| Line 763: | Line 771: | ||
| from vibration, abrasion, or liquids in conduits. In addition, it is essential that | from vibration, abrasion, or liquids in conduits. In addition, it is essential that | ||
| the following practices be adhered to: | the following practices be adhered to: | ||
| + | |||
| A. Never run sensor wires in the same conduit with ignition wiring or | A. Never run sensor wires in the same conduit with ignition wiring or | ||
| other high energy wiring such as AC line power. | other high energy wiring such as AC line power. | ||
| + | |||
| B. Keep secondary wires to spark plugs and other high voltage wiring at | B. Keep secondary wires to spark plugs and other high voltage wiring at | ||
| least eight inches (200mm) away from sensor and sensor wiring. | least eight inches (200mm) away from sensor and sensor wiring. | ||
| Line 773: | Line 783: | ||
| connect to the terminal module. Use stranded thermocouple wire having a | connect to the terminal module. Use stranded thermocouple wire having a | ||
| moisture-resistant insulation such as PVC. For higher ambient temperatures, | moisture-resistant insulation such as PVC. For higher ambient temperatures, | ||
| - | DE-4000 II 11-19 | + | Teflon or B-fiber insulated thermocouple wire is recommended. To ensure that |
| - | All rights reserved © ALTRONIC, LLC 2019 15 | + | |
| - | Teflon or B-fibre insulated thermocouple wire is recommended. To ensure that | + | |
| an accurate signal is transmitted to the device, avoid any added junctions, | an accurate signal is transmitted to the device, avoid any added junctions, | ||
| splices and contact with other metals. On unused channels, leave the shunt | splices and contact with other metals. On unused channels, leave the shunt | ||
| Line 781: | Line 789: | ||
| abrasion, or liquids in conduits. In addition, it is essential that the following | abrasion, or liquids in conduits. In addition, it is essential that the following | ||
| practices be adhered to: | practices be adhered to: | ||
| + | |||
| A. Never run sensor wires in the same conduit with ignition wiring or | A. Never run sensor wires in the same conduit with ignition wiring or | ||
| other high energy wiring such as AC line power. | other high energy wiring such as AC line power. | ||
| + | |||
| B. Keep secondary wires to spark plugs and other high voltage wiring at | B. Keep secondary wires to spark plugs and other high voltage wiring at | ||
| least eight inches (200mm) away from sensor and sensor wiring. | least eight inches (200mm) away from sensor and sensor wiring. | ||
| Line 804: | Line 814: | ||
| monitoring the engine flywheel or other rotating gears. Each speed input is | monitoring the engine flywheel or other rotating gears. Each speed input is | ||
| protected from mis-wires of up to 200 volts max. | protected from mis-wires of up to 200 volts max. | ||
| + | |||
| The RPMx- terminals are common to DC-. Connect the speed input to the | The RPMx- terminals are common to DC-. Connect the speed input to the | ||
| terminals marked RPMx+ and RPMx-. Altronic magnetic pickups or Hall effect | terminals marked RPMx+ and RPMx-. Altronic magnetic pickups or Hall effect | ||
| pickups are typical sources for RPM measurement. | pickups are typical sources for RPM measurement. | ||
| - | # MAGNETIC PICKUP – Connect the two wires from the 691118 series or | + | |
| + | ● MAGNETIC PICKUP – Connect the two wires from the 691118 series or | ||
| similar magnetic pickup to the module at terminals RPMx+ and RPMx- using cable assembly 693104 series. | similar magnetic pickup to the module at terminals RPMx+ and RPMx- using cable assembly 693104 series. | ||
| - | # HALL EFFECT PICKUP – Connect the three wires from the 791050 series | + | |
| + | ● HALL EFFECT PICKUP – Connect the three wires from the 791050 series | ||
| Hall effect pickup to the module at terminals RPMx+, RPMx-, and a +5 volt | Hall effect pickup to the module at terminals RPMx+, RPMx-, and a +5 volt | ||
| source using cable assembly 593050 series. Connect pickup cable wire B | source using cable assembly 593050 series. Connect pickup cable wire B | ||
| Line 823: | Line 836: | ||
| keypad to the Controller Module. Wire each connection from the Controller | keypad to the Controller Module. Wire each connection from the Controller | ||
| Module to the Display Module as follows: | Module to the Display Module as follows: | ||
| - | # STOP (+) to STOP (terminal 7) | + | |
| - | # RESET (+) to RESET (terminal 8) | + | ● STOP (+) to STOP (terminal 7)\\ |
| - | # START (+) to START (terminal 9) | + | ● RESET (+) to RESET (terminal 8)\\ |
| - | # STOP (-) to MINUS(-) (terminal 10) | + | ● START (+) to START (terminal 9)\\ |
| + | ● STOP (-) to MINUS(-) (terminal 10)\\ | ||
| The STOP, RESET, and START inputs on the Controller Module can also be | The STOP, RESET, and START inputs on the Controller Module can also be | ||
| connected to normally-open, | connected to normally-open, | ||
| Line 832: | Line 847: | ||
| activated when switched to (-). | activated when switched to (-). | ||
| + | < | ||
| + | <p style=" | ||
| + | < | ||
| + | only is required from the Controller | ||
| + | Module to the Display Module; all | ||
| + | (-) connections on the Controller | ||
| + | Module are common. | ||
| + | |||
| + | </p> | ||
| + | </ | ||
| ==== - CONTROLLER MODULE OUTPUT SWITCH WIRING ==== | ==== - CONTROLLER MODULE OUTPUT SWITCH WIRING ==== | ||
| The Controller Module has four discrete outputs rated 52VDC, 1.2 amp max. | The Controller Module has four discrete outputs rated 52VDC, 1.2 amp max. | ||
| Line 845: | Line 870: | ||
| be wired as high-side or low-side configurations. The output switches will be in | be wired as high-side or low-side configurations. The output switches will be in | ||
| the open (de-energized) condition when the unit is not powered. | the open (de-energized) condition when the unit is not powered. | ||
| - | DSO1 – FUEL SHUTOFF: Typical use of Output 1 on the Controller Module | + | |
| + | **DS01** | ||
| is for fuel shutoff. Output 1 can be used to control a 12-24 volt fuel | is for fuel shutoff. Output 1 can be used to control a 12-24 volt fuel | ||
| valve either as energized to run or pulsed to shut off. | valve either as energized to run or pulsed to shut off. | ||
| - | DO NOT attempt to control a C.D.-powered fuel valve directly with any | + | |
| + | **DO NOT** attempt to control a C.D.-powered fuel valve directly with any | ||
| of the DSOx output switches. The C.D. ignition system exceeds the | of the DSOx output switches. The C.D. ignition system exceeds the | ||
| max operating voltage of the output switch. An interposing relay and | max operating voltage of the output switch. An interposing relay and | ||
| a Murphy Panel Board Adapter must be used when the Fuel Valve is a | a Murphy Panel Board Adapter must be used when the Fuel Valve is a | ||
| C.D. ignition-type Murphy Fuel Valve. | C.D. ignition-type Murphy Fuel Valve. | ||
| - | DS02 – IGNITION SHUTDOWN: Typical use of Output 2 on the Controller | + | |
| + | **DS02** – IGNITION SHUTDOWN: Typical use of Output 2 on the Controller | ||
| Module is for Ignition Shutdown. Output 2 can be used in conjunction | Module is for Ignition Shutdown. Output 2 can be used in conjunction | ||
| with the low voltage shutdown on most Altronic ignition systems. In | with the low voltage shutdown on most Altronic ignition systems. In | ||
| addition DSO2 can be used to control the source power to the ignition | addition DSO2 can be used to control the source power to the ignition | ||
| system using a Power Management Module. | system using a Power Management Module. | ||
| - | DO NOT attempt to directly ground-out (stop) a C.D. ignition system | + | |
| + | **DO NOT** attempt to directly ground-out (stop) a C.D. ignition system | ||
| with output DSO2. The C.D. ignition system shutdown lead exceeds | with output DSO2. The C.D. ignition system shutdown lead exceeds | ||
| the max operating voltage of output switch DSO2. An interposing relay | the max operating voltage of output switch DSO2. An interposing relay | ||
| with high current contacts must be used when grounding the shutdown lead on a C.D. ignition system. | with high current contacts must be used when grounding the shutdown lead on a C.D. ignition system. | ||
| - | DO NOT connect directly to the ignition system common coil ground. | + | |
| - | DSO3 – CRANK DISCONNECT: Typical use of Output 3 on the Controller Module is for crank disconnect. When auto start is configured, | + | **DO NOT** connect directly to the ignition system common coil ground. |
| + | |||
| + | **DS03** | ||
| digital output 3 is used for crank disconnect. If the voltage or current | digital output 3 is used for crank disconnect. If the voltage or current | ||
| requirement of the crank disconnect solenoid is greater than 52VDC or | requirement of the crank disconnect solenoid is greater than 52VDC or | ||
| 1.2 amp, wire DS03 to a pilot duty relay. | 1.2 amp, wire DS03 to a pilot duty relay. | ||
| - | DSO4 – PRELUBE/ | + | |
| + | **DSO4** – PRELUBE/ | ||
| Module is for prelube/ | Module is for prelube/ | ||
| of the prelube/ | of the prelube/ | ||
| Line 874: | Line 906: | ||
| ==== - RS-485 COMMUNICATIONS WIRING ==== | ==== - RS-485 COMMUNICATIONS WIRING ==== | ||
| There are two RS-485 communication ports available on the Controller Module: | There are two RS-485 communication ports available on the Controller Module: | ||
| + | |||
| RS485 1 port is used for Modbus slave data | RS485 1 port is used for Modbus slave data | ||
| + | |||
| RS485 2 is used for Modbus master data. | RS485 2 is used for Modbus master data. | ||
| + | |||
| The DE-4000 System can communicate to other instruments, | The DE-4000 System can communicate to other instruments, | ||
| via the two serial RS-485 communication wires. Use a two-conductor | via the two serial RS-485 communication wires. Use a two-conductor | ||
| Line 1047: | Line 1082: | ||
| | 40319 | 40320 | T5: | | 40319 | 40320 | T5: | ||
| - | ^ PID1 ^^^ | + | ^ PID1 |
| + | ^ Register | ||
| + | | 40400:\\ 40401 | Enable | ||
| + | | 40402:\\ 40403 | P-Factor | ||
| + | | 40404:\\ 40405 | I-Factor | ||
| + | | 40406:\\ 40407 | D-Factor | ||
| + | | 40408:\\ 40409 | Max Limit | | ::: | 40438:\\ 40439 | Max Limit | | | ||
| + | | 40410:\\ 40411 | Min Limit | | ::: | 40440:\\ 40441 | Min Limit | | | ||
| + | | 40412:\\ 40413 | Input\\ Terminal | ||
| + | | 40414:\\ 40415 | Input\\ Channel | ||
| + | | 40416:\\ 40417 | Output\\ Terminal | ||
| + | | 40418:\\ 40419 | Output\\ Channel | ||
| + | | 40420:\\ 40421 | Deadband | ||
| + | | 40422:\\ 40423 | Setpoint | ||
| + | |||
| + | ^ PID3 ^^^ ^ PID4 ^^^ | ||
| + | ^ Register | ||
| + | | 40460:\\ 40461 | Enable | ||
| + | | 40462:\\ 40463 | P-Factor | ||
| + | | 40464:\\ 40465 | I-Factor | ||
| + | | 40466:\\ 40467 | D-Factor | ||
| + | | 40468:\\ 40469 | Max Limit | | ::: | 40498:\\ 40499 | Max Limit | | | ||
| + | | 40470:\\ 40471 | Min Limit | | ::: | 40500:\\ 40501 | Min Limit | | | ||
| + | | 40472:\\ 40473 | Input\\ Terminal | ||
| + | | 40474:\\ 40475 | Input\\ Channel | ||
| + | | 40476:\\ 40477 | Output\\ Terminal | ||
| + | | 40478:\\ 40479 | Output\\ Channel | ||
| + | | 40480:\\ 40481 | Deadband | ||
| + | | 40482:\\ 40483 | Setpoint | ||
| + | |||
| + | ^ PID5 ^^^ ^ PID6 ^^^ | ||
| + | ^ Register | ||
| + | | 40520:\\ 40521 | Enable | ||
| + | | 40522:\\ 40523 | P-Factor | ||
| + | | 40524:\\ 40525 | I-Factor | ||
| + | | 40526:\\ 40527 | D-Factor | ||
| + | | 40528:\\ 40529 | Max Limit | | ::: | 40558:\\ 40559 | Max Limit | | | ||
| + | | 40530:\\ 40531 | Min Limit | | ::: | 40560:\\ 40561 | Min Limit | | | ||
| + | | 40532:\\ 40533 | Input\\ Terminal | ||
| + | | 40534:\\ 40535 | Input\\ Channel | ||
| + | | 40536:\\ 40537 | Output\\ Terminal | ||
| + | | 40538:\\ 40539 | Output\\ Channel | ||
| + | | 40540:\\ 40541 | Deadband | ||
| + | | 40542:\\ 40543 | Setpoint | ||
| + | |||
| + | ^ PID7 ^^^ ^ PID8 ^^^ | ||
| + | ^ Register | ||
| + | | 40580:\\ 40581 | Enable | ||
| + | | 40582:\\ 40583 | P-Factor | ||
| + | | 40584:\\ 40585 | I-Factor | ||
| + | | 40586:\\ 40587 | D-Factor | ||
| + | | 40588:\\ 40589 | Max Limit | | ::: | 40618:\\ 40619 | Max Limit | | | ||
| + | | 40590:\\ 40591 | Min Limit | | ::: | 40620:\\ 40621 | Min Limit | | | ||
| + | | 40592:\\ 40593 | Input\\ Terminal | ||
| + | | 40594:\\ 40595 | Input\\ Channel | ||
| + | | 40596:\\ 40597 | Output\\ Terminal | ||
| + | | 40598:\\ 40599 | Output\\ Channel | ||
| + | | 40600:\\ 40601 | Deadband | ||
| + | | 40602:\\ 40603 | Setpoint | ||
| + | |||
| + | ^ PID9 ^^^ ^ PID10 ^^^ | ||
| + | ^ Register | ||
| + | | 40640:\\ 40641 | Enable | ||
| + | | 40642:\\ 40643 | P-Factor | ||
| + | | 40644:\\ 40645 | I-Factor | ||
| + | | 40646:\\ 40647 | D-Factor | ||
| + | | 40648:\\ 40649 | Max Limit | | ::: | 40678:\\ 40679 | Max Limit | | | ||
| + | | 40650:\\ 40651 | Min Limit | | ::: | 40680:\\ 40681 | Min Limit | | | ||
| + | | 40652:\\ 40653 | Input\\ Terminal | ||
| + | | 40654:\\ 40655 | Input\\ Channel | ||
| + | | 40656:\\ 40657 | Output\\ Terminal | ||
| + | | 40658:\\ 40659 | Output\\ Channel | ||
| + | | 40660:\\ 40661 | Deadband | ||
| + | | 40662:\\ 40663 | Setpoint | ||
| + | |||
| + | ^ Key Command Registers | ||
| + | | Register | ||
| + | | 40700 | Main Key Command Register\\ Write 1 for Star\\ Write 2 for Reset\\ Write 3 for Stop\\ Write 4 for Cancel Timers | ||
| + | | 40701 | Start Key Command\\ (Write any value to start) | ||
| + | | 40702 | Reset Key Command\\ (Write any value to reset) | ||
| + | | 40703 | Stop Key Command\\ (Write any value to stop) | | ||
| + | | 40704 | Cancel Timers Key Command\\ (Write any value to Cancel Timers) | ||
| + | | Key Commands are 16-Bit Registers | ||
| + | |||
| + | ^ Global/ | ||
| ^ Register | ^ Register | ||
| - | | | + | | |
| - | | | + | | |
| - | | | + | | |
| - | | | + | | |
| - | | | + | | |
| - | | | + | | |
| - | | | + | | |
| - | | | + | | 40814:\\ 40815 | Input #2\\ Linear/ |
| - | | | + | | 40816:\\ 40817 | Input #1\\ Terminal |
| - | | | + | | |
| - | | | + | | |
| - | | | + | | 40822:\\ 40823 | Input #2\\ Channel |
| + | | 40824:\\ 40825 | ||
| + | | | ||
| + | | | ||
| + | | 40830:\\ 40831 | Output #2\\ Channel | ||
| + | | 40832:\\ 40833 | Output #1\\ Low | ||
| + | | | ||
| + | | 40836:\\ 40837 | Output #2\\ Low | | | ||
| + | | 40838:\\ 40839 | Output #2\\ High | | | ||
| + | | 40840:\\ 40841 | Output #1\\ Ramp Rate | | | ||
| + | | 40842:\\ 40843 | Output #2\\ Ramp Rate | | | ||
| + | | 40844:\\ 40845 | Output #1\\ Reverse Action | ||
| + | | 40846:\\ 40847 | Output #2\\ Reverse Action | ||
| + | | 40848:\\ 40849 | Input #1\\ P-Factor | ||
| + | | 40850:\\ 40851 | Input #1\\ I-Factor | ||
| + | | 40852:\\ 40853 | Input #1\\ D-Factor | ||
| + | | 40854:\\ 40855 | Input #2\\ P-Factor | ||
| + | | 40856:\\ 40857 | Input #2\\ I-Factor | ||
| + | | 40858:\\ 40859 | Input #2\\ D-Factor | ||
| + | | 40860:\\ 40861 | Auto/Manual Toggle\\ Input Terminal | ||
| + | | 40862:\\ 40863 | Auto/Manual Toggle\\ Input Channel | ||
| + | | 40864:\\ 40865 | Speed Control\\ Mode | 0=Manual\\ 1=Auto | ||
| + | | 40866:\\ 40867 | Manual\\ Speed | value in\\ RPM | | ||
| + | |||
| + | Registers 41001 - 41998 are the Register Mirror Test Area(Any value written to these registers will be able to be read starting at register 30001. For example you can write a 32 bit value at 41001,41002 and read it at 30001, 30002) | ||
| + | |||
| + | Starting at register 42000:42001 The Safety Setpoint for each channel is store. First High then Low.\\ | ||
| + | Example: 42000:42001 is Terminal 1 Input 1 High Safety Setpoint and 42002:42003 is Terminal 1 Input 1 Low Safety Setpoint. | ||
| + | |||
| + | There is 100 register spacing between channels so Terminal 1 Input 2 High and Low Safety Setpoints are registers 42100:42101 and 42102: | ||
| + | |||
| + | This continues for 32 channels per terminal board with 5 Terminal Boards Max | ||
| ===== - HAZARDOUS AREA OPERATION ===== | ===== - HAZARDOUS AREA OPERATION ===== | ||
| - | ==== - ==== | + | ==== - General |
| The DE-4000 Series Configurable Safety Shutdown and Control System is CSA | The DE-4000 Series Configurable Safety Shutdown and Control System is CSA | ||
| (C/US) – certified for Class I, Division 2, Groups C and D areas or non-hazardous | (C/US) – certified for Class I, Division 2, Groups C and D areas or non-hazardous | ||
| locations. | locations. | ||
| - | # The HMI Display Module is CSA certified (C/US) with an ambient temperature range of -30°C to 80°C (-22°F to 176°F) temperature code T4 | + | |
| - | # The Controller Module is CSA certified (C/US) with an ambient temperature | + | ● The HMI Display Module is CSA certified (C/US) with an ambient temperature range of -30°C to 80°C (-22°F to 176°F) temperature code T4 |
| + | |||
| + | ● The Controller Module is CSA certified (C/US) with an ambient temperature | ||
| range of -40°C to 85°C (-40°F to 185°F) temperature code T4 | range of -40°C to 85°C (-40°F to 185°F) temperature code T4 | ||
| - | # The Terminal Module is CSA certified (C/US) with an ambient temperature | + | |
| + | ● The Terminal Module is CSA certified (C/US) with an ambient temperature | ||
| range of -40°C to 85°C (-40°F to 185°F) temperature code T3C | range of -40°C to 85°C (-40°F to 185°F) temperature code T3C | ||
| + | |||
| The DE-4000 System must be installed in a suitable enclosure. | The DE-4000 System must be installed in a suitable enclosure. | ||
| + | |||
| The following requirements must also be met (refer to NFPA standard no. 493): | The following requirements must also be met (refer to NFPA standard no. 493): | ||
| - | # The low voltage sensor switch wires within the panel enclosure must be kept | + | |
| + | ● The low voltage sensor switch wires within the panel enclosure must be kept | ||
| at least two (2) inches away from other wiring. Run the sensor switch wires | at least two (2) inches away from other wiring. Run the sensor switch wires | ||
| leaving the panel in a separate conduit from all other wiring and keep them | leaving the panel in a separate conduit from all other wiring and keep them | ||
| separate throughout the installation. | separate throughout the installation. | ||
| - | # Wiring to the sensors must have a grade of insulation capable of withstanding | + | |
| + | ● Wiring to the sensors must have a grade of insulation capable of withstanding | ||
| an AC voltage of 500 volts RMS. | an AC voltage of 500 volts RMS. | ||
| - | # Sensor wires must be run in separate conduits and junction boxes from high | + | |
| + | ● Sensor wires must be run in separate conduits and junction boxes from high | ||
| voltage wires such as ignition, fuel valve, and other high voltage wiring. | voltage wires such as ignition, fuel valve, and other high voltage wiring. | ||
| - | ==== - ==== | + | < |
| + | <p style=" | ||
| + | < | ||
| + | components may impair intrinsic | ||
| + | safety and/or suitability for Class | ||
| + | I, Div. 2, Groups C and D. Do | ||
| + | not disconnect equipment in Div. | ||
| + | 2 environment unless power is | ||
| + | switched off or the area is known to | ||
| + | be non-hazardous. | ||
| + | |||
| + | </ | ||
| + | </ | ||
| + | ==== - Power ==== | ||
| The power for the DE-4000 System must be from a Class 2 power source with | The power for the DE-4000 System must be from a Class 2 power source with | ||
| transient protection or from a 24-volt battery system. | transient protection or from a 24-volt battery system. | ||
| + | |||
| The DE-4000 System must be installed in accordance with the requirements of | The DE-4000 System must be installed in accordance with the requirements of | ||
| the National Electrical Code (US) and the Canadian Electrical Code (Canada) | the National Electrical Code (US) and the Canadian Electrical Code (Canada) | ||
| - | ==== - ==== | + | ==== - WARNINGS |
| - | WARNINGS | + | |
| - | # WARNING – EXPLOSION HAZARD – Substitution of components may impair | + | ● WARNING – EXPLOSION HAZARD – Substitution of components may impair |
| intrinsic safety and/or suitability for Class 1, Div. 2, Groups C and D. | intrinsic safety and/or suitability for Class 1, Div. 2, Groups C and D. | ||
| - | # AVERTISSEMENT – RISQUE D’EXPLOSION – La substitution de composants eutrendre ce materiel inacceptable pour les emplacements de Classe I, Division 2. | + | |
| - | # WARNING – EXPLOSION HAZARD – Do not disconnect equipment in Div. | + | ● AVERTISSEMENT – RISQUE D’EXPLOSION – La substitution de composants eutrendre ce materiel inacceptable pour les emplacements de Classe I, Division 2. |
| + | |||
| + | ● WARNING – EXPLOSION HAZARD – Do not disconnect equipment in Div. | ||
| 2 environment unless power is switched off or the area is known to be nonhazardous. | 2 environment unless power is switched off or the area is known to be nonhazardous. | ||
| - | # AVERTISSEMENT – RISQUE D’EXPLOSION – Avant de deconnecter l’equipement, | + | |
| + | ● AVERTISSEMENT – RISQUE D’EXPLOSION – Avant de deconnecter l’equipement, | ||
| couper le courant ou s’assurer que l’emplacement est designe non. | couper le courant ou s’assurer que l’emplacement est designe non. | ||
| - | # Warning – EXPLOSION HAZARD - Do not use USB connectors in hazardous area. | + | |
| - | # AVERTISSEMENT – RISQUE D’EXPLOSION – Ne pas utiliser les connecteurs | + | ● Warning – EXPLOSION HAZARD - Do not use USB connectors in hazardous area. |
| + | |||
| + | ● AVERTISSEMENT – RISQUE D’EXPLOSION – Ne pas utiliser les connecteurs | ||
| USB en zone dangereuse. | USB en zone dangereuse. | ||
| - | ==== - ==== | + | ==== - IP54 ==== |
| When the DE-4000 System is installed in hazardous area, it shall be installed | When the DE-4000 System is installed in hazardous area, it shall be installed | ||
| in a suitable enclosure which provides an ingress protection minimum level of | in a suitable enclosure which provides an ingress protection minimum level of | ||
| IP54 (splash protected). | IP54 (splash protected). | ||
| - | ==== - ==== | + | ==== - Inputs |
| The inputs are rated non-incendive: | The inputs are rated non-incendive: | ||
| - | # Terminal Module – when the inputs are configured as: | + | |
| - | • “Discrete” or “Digital” inputs must be connected to passive switches only. | + | ● Terminal Module – when the inputs are configured as: |
| - | • When configured as thermocouple, | + | |
| - | • When connected as an analog input, inputs must not exceed 5VDC. | + | • “Discrete” or “Digital” inputs must be connected to passive switches only.\\ |
| - | • When connected as 4-20mA, inputs must not exceed 24mA. | + | • When configured as thermocouple, |
| - | # RPM inputs – when connected to Altronic 691118-x magnetic pickup or | + | • When connected as an analog input, inputs must not exceed 5VDC.\\ |
| + | • When connected as 4-20mA, inputs must not exceed 24mA.\\ | ||
| + | ● RPM inputs – when connected to Altronic 691118-x magnetic pickup or | ||
| Altronic 791050-x Hall Effect pickup. Both pickups are CSA approved as | Altronic 791050-x Hall Effect pickup. Both pickups are CSA approved as | ||
| - | non-incendive outputs. | + | non-incendive outputs.\\ |
| - | # Controller Module Discrete Inputs – when connected to dry contacts. | + | ● Controller Module Discrete Inputs – when connected to dry contacts. |
| + | |||
| + | ==== - WiFi Antenna ==== | ||
| - | ==== - ==== | + | Coaxial cable leaving the system enclosure shall be routed in |
| - | WiFi Antenna – Coaxial cable leaving the system enclosure shall be routed in | + | |
| conduit or be protected by another approved Division 2 wiring method. The antenna itself shall be located in a non-hazardous area, or shall not have exposed | conduit or be protected by another approved Division 2 wiring method. The antenna itself shall be located in a non-hazardous area, or shall not have exposed | ||
| bare metal elements. | bare metal elements. | ||
| Line 1129: | Line 1309: | ||
| ===== - CONNECTING VIA ETHERNET TO CONFIGURE THE DE-4000 ===== | ===== - CONNECTING VIA ETHERNET TO CONFIGURE THE DE-4000 ===== | ||
| - | ==== - ==== | + | ==== - General |
| Each DE-4000 System requires configuration prior to use. The DE-4000 is a | Each DE-4000 System requires configuration prior to use. The DE-4000 is a | ||
| web-enabled smart device. Configuration of the DE-4000 is through the web | web-enabled smart device. Configuration of the DE-4000 is through the web | ||
| Line 1136: | Line 1316: | ||
| with a standard RJ45 connector on both ends, is required. Ethernet Cable, | with a standard RJ45 connector on both ends, is required. Ethernet Cable, | ||
| CAT5 1.0m (39") (693221-2) is a suitable cable available from Altronic. | CAT5 1.0m (39") (693221-2) is a suitable cable available from Altronic. | ||
| + | |||
| A network connection is required to connect the laptop PC to the DE-4000. | A network connection is required to connect the laptop PC to the DE-4000. | ||
| This can be accomplished in one of two ways, a temporary change to the TCP/ | This can be accomplished in one of two ways, a temporary change to the TCP/ | ||
| Line 1144: | Line 1325: | ||
| adapter is outlined below for Microsoft® Windows-based computers. The laptop | adapter is outlined below for Microsoft® Windows-based computers. The laptop | ||
| PC must have at least one Network Interface Card (NIC) installed. | PC must have at least one Network Interface Card (NIC) installed. | ||
| - | # IP Address 98.102.65.174 is the default IP address for the DE-4000 System. | + | |
| - | # The IP address of your laptop PC network interface must be set to an address of 98.102.65.x, | + | ● IP Address 98.102.65.174 is the default IP address for the DE-4000 System.\\ |
| - | range of 160-174. | + | ● The IP address of your laptop PC network interface must be set to an address of 98.102.65.x, |
| - | # The IP address on your laptop PC must be set to static. The PC is typically | + | ● The IP address on your laptop PC must be set to static. The PC is typically |
| configured to obtain an IP address dynamically; | configured to obtain an IP address dynamically; | ||
| - | no control over its address and will have to set it to static. | + | no control over its address and will have to set it to static.\\ |
| - | Follow the procedure below for Microsoft® Windows 7 operating system: | + | Follow the procedure below for Microsoft® Windows 7 operating system:\\ |
| - | 1. From the Microsoft® Windows 7 desktop, click on the Windows Button in | + | 1. From the Microsoft® Windows 7 desktop, click on the **Windows Button** in |
| - | the lower left-hand corner and then click on Control Panel. | + | the lower left-hand corner and then click on **Control Panel**. |
| - | 2. Click on Network and Sharing Center. | + | |
| - | 3. Click on Local Area Connection. | + | 2. Click on **Network and Sharing Center**. |
| - | 4. Click on the Properties button. | + | |
| - | 5. Click on the Internet Protocol Version 4 (TCP/IPv4) item and click on the | + | 3. Click on **Local Area Connection**. |
| - | Properties button. | + | |
| - | 6. Click on the Use the following IP address: option. | + | 4. Click on the **Properties** button. |
| + | |||
| + | 5. Click on the **Internet Protocol Version 4 (TCP/IPv4)** item and click on the | ||
| + | **Properties** button. | ||
| + | |||
| + | 6. Click on the **Use the following IP address:** option. | ||
| 7. Change the IP address to 98.102.65.xxx (for example 98.102.65.115). | 7. Change the IP address to 98.102.65.xxx (for example 98.102.65.115). | ||
| + | |||
| 8. Change the Subnet Mask to 255.255.255.0. | 8. Change the Subnet Mask to 255.255.255.0. | ||
| - | 9. Click OK. | + | |
| - | 10. Click OK on the Local Area Connection Properties screen. | + | 9. Click **OK**. |
| - | 11. Click Close on the Local Area Connection Status screen. | + | |
| + | 10. Click **OK** on the Local Area Connection Properties screen. | ||
| + | |||
| + | 11. Click **Close** on the Local Area Connection Status screen. | ||
| For further information, | For further information, | ||
| - | # A web browser on the laptop PC is used to communicate to the DE-4000 | + | |
| + | ● A web browser on the laptop PC is used to communicate to the DE-4000 | ||
| System. Preferred browsers are Google® Chrome and Firefox. | System. Preferred browsers are Google® Chrome and Firefox. | ||
| - | # Open the web browser and type in the IP address (98.102.65.174). The DE4000 configuration page will be loaded. | + | |
| + | ● Open the web browser and type in the IP address (98.102.65.174). The DE4000 configuration page will be loaded. | ||
| ===== - List of Figures ===== | ===== - List of Figures ===== | ||